If you cannot locate the official BR 5016 PDF, contact directly with the exact serial number printed on the unit’s side label. They often supply legacy documentation as a courtesy to existing users.
Selectable from 1 to 600 seconds.
: Ability to program specific steps as "fixed" for constant transformer compensation. Power Factor Controller - TDK Electronics
By following these recommendations, users can maximize the benefits of the Epcos Power Factor Controller Br 5016 and achieve significant energy savings.
| Display Code | Meaning | Action per Manual | | :--- | :--- | :--- | | AL. 1 | Undercurrent | Load current below 5% of CT rating. Check if main breaker is open. | | AL. 2 | Overvoltage | Voltage > 110% of nominal. Check grid stability or tap changer. | | AL. 3 | Undervoltage | Voltage < 80% of nominal. Brownout condition. | | AL. 4 | Over-temperature | Internal temperature > 70°C. Clean air vents or reduce switching cycles. | | AL. 7 | THD overload | Harmonic distortion > 10%. Install a detuned reactor or filter. | | c-- flashing | Wrong target power factor | The actual Cos φ is too capacitive. Reduce capacitor steps. |
Access parameters by pressing the Auto Program button. Passwords can be enabled or disabled in the "General" menu.